IBM 53962KX Datasheet Page 6

  • Download
  • Add to my manuals
  • Print
  • Page
    / 21
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 5
IBM 1000VA and 1500VA LCD Tower UPS 6
Specifications
Table 4 lists the specifications for the IBM 1000VA and 1500VA LCD Tower UPS models.
Table 4. Specifications
Specification IBM 1000VA
LCD Tower
UPS (100 V)
IBM 1000VA
LCD Tower
UPS (120 V)
IBM 1000VA
LCD Tower
UPS (230 V)
IBM 1500VA
LCD Tower
UPS (100 V)
IBM 1500VA
LCD Tower
UPS (120 V)
IBM 1500VA
LCD Tower
UPS (230 V)
IBM part
number
53961JX 53961AX 53961KX 53962JX 53962AX 53962KX
VA/Watts
rating
1000 VA / 750 W 1500 VA / 1000 W
Nominal
output voltage
(VAC)
100 VAC 120 VAC 230 VAC 100 VAC 120 VAC 230 VAC
Load groups Two load groups (load segments): Two outlets in load group 1, six outlets in load group 2
Output
connections
Eight NEMA
5-15R
Eight NEMA
5-15R
Eight IEC 320
C13
Eight NEMA
5-20R
Eight NEMA
5-15R
Eight IEC 320
C13
Input
Nominal input
voltage
100 VAC 120 VAC 230 VAC 100 VAC 120 VAC 230 VAC
Input
frequency
(auto sensing)
50/60 Hz +/- 3 Hz
Input
connection
type
IEC 320 C14 IEC 320 C14 IEC 320 C14 IEC 320 C20 IEC 320 C14 IEC 320 C14
Supplied Input
cords
IEC 320 C13
to JIS C-8303
2.8 m
IEC 320 C13
to NEMA
5-15P 2.8 m
None (see
Table 3.)
IEC 320 C19
to JIS C-8303
2.5 m
IEC 320 C13
to NEMA
5-15P 2.8 m
None (see
Table 3.)
Input voltage
range, mains
operations
84 - 121 V 97 - 145 V 160 - 286 V 84 - 121 V 97 - 145 V 160 - 286 V
Batteries
Typical
backup times
See Table 5 See Table 6
Battery type Valve Regulated Lead Acid (VRLA)
maintenance-free, sealed, leak-proof
Optional
External
Battery Pack
No No No No No No
Typical
recharge time
4 hours to 90% charge from a UPS/battery discharge of 50% rated load
Page view 5
1 2 3 4 5 6 7 8 9 10 11 ... 20 21

Comments to this Manuals