IBM 1000VA and 1500VA LCD Tower UPS 8
Table 6 lists the expected period that the IBM 1500VA LCD Tower UPS models will operate solely on
batteries.
Table 6. IBM 1500VA LCD Tower UPS runtime chart
Load (%) Load (VA) Load (Watts) Run time (minutes)
25 375 VA 255 W 36
50 750 VA 510 W 15
75% 1125 VA 750 W 9
100% 1500 VA 970 W 6
Note: Battery backup times are approximate and may vary with equipment, configuration, battery age,
and temperature. The IBM 1000VA and 1500VA LCD Tower UPS models do not support Extended
Battery Modules (EBMs).
Physical specifications
Height: 246 mm (9.7 in.)
Width: 160 mm (6.3 in.)
Depth: 436 mm (17.2 in.)
Weight: 1000VA models: 14 kg (32 lb); 1500VA models: 19 kg (42 lb)
Operating environment
The IBM 1000VA and 1500VA LCD Tower UPS models are supported in the following environment:
Temperature (operation): 0 to 40 °C (32 to 104 °F)
Relative humidity: 5 to 95%
Maximum altitude (operation): 3,000 m (10,000 ft)
Warranty
The IBM 1000VA and 1500VA LCD Tower UPS models have a three-year limited warranty. Optional
features have a one-year warranty
Front panel controls
With a bright and easy-to-navigate panel that provides configurability and displays important status
information, the IBM 1000VA and 1500VA LCD Tower UPS models are easy to manage and an ideal
solution for standardization across the global enterprise. Runtime, load, and other vital information and
troubleshooting are also displayed.
Figure 2 shows the front panel of the UPS.